Flue gas condensation HEGC-CD-0400
ith depluming system for biomass boiler 4.000 kW
By installing the heat recovery system HEGC-CD-0400, the moist exhaust gas of the biomass boiler is also used thermally by cooling in a condenser.
The heat content of the exhaust gases is converted directly into useful heat for two heating networks in a smooth-tube heat exchanger made of high-quality stainless steel 1.4571. In addition to heat extraction, the HEGC-CD-0400 also has a dedusting effect. A degree of dedusting of approx. 50-60% can be assumed.
Key data:
- CONDENSER (district heating system)
- CONDENSER
Heat output CONDENSER 889 kW (w50, 47°C RT) - Welded stainless steel AIR PREHEATER
Heat output AIR PREHEATER 287 kW - All heat exchanger pipes made of stainless steel 1.4462
- Housing parts, process tank as well as pipe & channel
parts made of stainless steel 1.4571 - Depluming fan 45 kW
- Connection to the existing flue gas system
- Stainless steel control cabinet
- Engineering (procedural layout & design)
- Isolation
- Assembly and Delivery
- Control with remote maintenance
- Startup
- Place of installationi: AUSTRIA